Diagnóstico de los factores microestructurales en el proceso de soldadura MIG/MAG que causan averías en los transformadores: estudio de caso

Abstract

The study examined microstructural factors in the MIG/MAG welding process of 3 mm and 4 mm industrial steel, leading to failures in 500 KVA power transformers. Charpy-V impact tests and microstructural analysis were conducted to correlate microstructure with impact toughness. Results revealed impurities in the weld pool, affecting weld quality and causing leaks of insulating oil.

Description

Keywords

Soldagem MIG/MAG, transformadores de potência, microestrutura, tenacidade ao impacto, análise metalográfica

Citation

LOPES, R. V. P.; COSTA, O. F. L.; FUJIYAMA, R. T.; PINTO, V. B.; LEITE, J. C. Diagnóstico de los factores microestructurales en el proceso de soldadura MIG/MAG que causan averías en los transformadores: estudio de caso. In: VII International Scientific Conference of Mechanical Engineering, 2012, Villa Clara. Anais... Villa Clara: 2012. p. 1-8.