    Barrido de Frecuencia en Coordenadas de Fase para Sistemas Desequilibrados
    (INSTITUTO DE TECNOLOGIA, 2012) CABRAL LEITE, Jandeey; TOSTES, Maria Emilia de Lima; PÉREZ ABRIL, Ignacio; MEDEIROS, Adelson Bezerra de; AZEVEDO, Manoel Socorro Santos; BEZERRA, Ubiratan Holanda; MAGALHÃES, Edilson Marques
    The paper develops a phase-coordinates model for analyzing unbalanced electrical networks, enabling the specification of single-phase or three-phase harmonic injections of any sequence. The model is applied to a four-wire delta system, demonstrating its ability to represent structural asymmetries and identify resonances at different frequencies.
  • Imagem de Miniatura
    Item
    Optimización Multiobjetivo de Filtros Pasivos
    (INSTITUTO DE TECNOLOGIA, 2012) LEITE, Jandecy Cabral; ABRIL, Ignacio Pérez; TOSTES, Maria Emilia de Lima; OLIVEIRA, Roberto Celio Limão de; MAGALHÃES, Edilson Marques
    Different approaches have been used to formulate the problem of passive filter design, classified into single or multi-objective formulations. While previous contributions solve the multi-objective problem by minimizing a single objective function composed of a weighted sum of sub-objectives, this work uses the Non-dominated Sorting Genetic Algorithm (NSGA-II) to address the problem. The developed program determines the number, location, configuration, and parameters of passive filters required to obtain non-dominated optimal solutions, considering four predefined filter types. The solution of a practical example demonstrates the effectiveness of the proposed procedure.
  • Imagem de Miniatura
    Item
    Proposta de um algoritmo para diagnosticar a qualidade de energia elétrica utilizando lógica fuzzy
    (INSTITUTO DE TECNOLOGIA, 2010) GONÇALVES, Benevaldo Pereira; LEITE, Jandecy Cabral; COSTA JUNIOR, Carlos Tavares da; TOSTES, Maria Emilia de Lima; Eduardo de Magalhães Braga
    The article proposes a fuzzy logic-based algorithm to diagnose power quality in low-voltage three-phase systems using the THD (Total Harmonic Distortion) indicator. The fuzzy inference system classifies distortion levels in voltage and current, generating diagnoses such as "normal," "significant," or "critical." The method aims to assist in problem identification and decision-making to mitigate harmonic disturbances, contributing to improved power quality.